EVP Tower 3/3 TT 100KVA
Part Number: TLEVP100
High Reliability:
Online double conversion, 0.99 input power factor
Three-phase Input 400Vac, Three-phase Input 400VacEnergy-Saving & Compatibility:
ECO mode operation to reduce energy consumption.
Comprehensive Protection & Convenience:
Overload, overheating, short-circuit protection, intelligent cooling, and multiple interfaces.
- Recommended for Data Centers, Local Area Network (LAN ), Electro-medical, Industry processes, Virtual servers, Pellet stoves, Thermo-fireplaces, Boilers for home heating
- Intelligent slot for SNMP card o Dry Contact
- Compatibility with generating set
- Battery charging system managed by microprocessor
- Frequency converter mode
MODEL | TLEVP100 | TLEVP120 | TLEVP160 | TLEVP200 |
Capacity (VA/Watts) | 100k / 90k | 120k / 108k | 160k / 144k | 200k / 180k |
INPUT | ||||
Nominal voltage | 380/400/415Vac, (3Ph+N+PE) | |||
Operating voltage range | 138~485Vac for 40%load; 305~485Vac for full-load | |||
Operating frequency range | 40~70Hz | |||
Power factor | ≥0.99 | |||
Bypass voltage range | 220Vac Max.voltage: +25%(optional +10%,+15%,+20% ) 230Vac Max.voltage: +20%(optional +10%,+15% ) 240Vac Max.voltage: +15%(optional +10% ) Min. voltage: -45% (optional -20%,-30%) Frequency synchronize tracing range: ±10% |
|||
generator input | Support | |||
Harmonic distortion (THDi) | ≤3%(100% non-linear load) |
OUTPUT | ||
Rated voltage | 380/400/415Vac(3Ph+N+PE) | |
Power factor | 0.9 | |
Voltage regulation |
±1% | |
Frequency | Line mode | synchronize with input; when input frequency >±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz |
Bat. mode | 50/60(±0.1)Hz | |
Crest factor | 3:1 | |
Harmonic distortion (THDv) | ≤2% with linear load ≤4% with non-linear load |
|
Efficiency | 96% |
BATTERY | ||||
Battery voltage | Optional Voltage: ±180/±192/±204/±216/±228/±240/±252/±264/±276/±288/±300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional) 360Vdc~600Vdc (30~50 pcs, 30 pcs define, 32~50 pcs no power derating; 30 pcs output power factor 0.8;) |
|||
Charging current (A)(Charging current can be set according to battery capacity installed) |
40A (Max.) | 40A (Max.) | 60A (Max.) | 60A (Max.) |
SYSTEM FEATURES | |
Transfer time | Utility to Battery : 0ms; Utility to bypass: 0ms |
Overload | ≤110% overload 60 min; ≤150% overload 1 min,to Bypass Bypass mode:135% overload long time; >1000% overload 100 ms |
Backfeed protection | Support |
Alarm | Overload, utility abnormal, UPS fault, battery low, etc. |
Protection | Short circuit, overload, over temperature, battery low, fan fault alarm. |
Remote LCD | Support |
Communication interface |
USB, RS232, RS485, Parallel port, dry contact, Intelligent slot, LBS, SNMP card (optional), Relay card (optional) |
ENVIRONMENT | |||||
Operating temperature | 0~40℃ | ||||
Storage temperature |
25~55℃(No battery) | ||||
Humidity range | 0~95% (Non-condensing) | ||||
Altitude | <1500m. When >1500m, derating power for use | ||||
Noise level | <62db | <63dB | <65dB | ||
PHYSICAL | |||||
Dimension D×W×H (mm) |
828×250×1100 | ||||
Net weight (kg) | 147 | 152 | 200 | 230 | |
STANDARDS | |||||
Safety | IEC/EN62040-1,IEC/EN60950-1 | ||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |