EVP PLUS T3 100.0

EVP PLUS T3 100.0

Part Number :TLEVP100

Desciption:

  • Complete protection from blackout, voltage fluctuations (overvoltages and undervoltages), lightning (with upstream arrester), frequency variations, surge, harmonics, voltage distortions
  • Recommended for Local Area Networks (LAN), Data Centers, Industry, Electromedical Equipments
  • Intelligent slot for SNMP, Dry Contact or MODBUS card
  • On-Line Double Conversion technology transformerless (VFI-SS-111)
  • Active PFC circuit (0.99)
  • Compatibility with generator
  • Static and manual bypass
  • Frequency converter mode
MODEL

TLEVP100

TLEVP120 TLEVP160

TLEVP200

Capacity (VA/Watts)

100k / 90k

120k / 108k 160k / 144k

200k / 180k

INPUT
Nominal voltage

380/400/415Vac, (3Ph+N+PE)

Operating voltage range

138~485Vac for 40%load; 305~485Vac for full-load

Operating frequency range

40~70Hz

Power factor

≥0.99

Bypass voltage range

220Vac Max.voltage: +25%(optional +10%,+15%,+20% )
230Vac Max.voltage: +20%(optional +10%,+15% )
240Vac Max.voltage: +15%(optional +10% )
Min. voltage: -45% (optional -20%,-30%)
Frequency synchronize tracing range: ±10%

generator input

Support

Harmonic distortion (THDi)

≤3%(100% non-linear load)

OUTPUT
Rated voltage

380/400/415Vac(3Ph+N+PE)

Power factor

0.9

Voltage
regulation

±1%

Frequency Line mode

synchronize with input; when input frequency >±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz

Bat. mode

50/60(±0.1)Hz

Crest factor

3:1

Harmonic distortion (THDv)

≤2% with linear load
≤4% with non-linear load

Efficiency

96%

BATTERY
Battery voltage

Optional Voltage: ±180V/±192V/±204V/±216V/±228V/±240/±252/±264/±276/±288/±300Vdc(30/32/34/36/38/40/42/44/
46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 30 pcs default, 36~50 pcs output power factor 1.0; 32~34 pcs output
power factor 0.9; 30 pcs output power factor 0.8;)

Charging current
(A)(Charging current can be set according to battery capacity installed)

 40A(Max.)

60A(Max.)

SYSTEM FEATURES
Transfer time

Utility to Battery : 0ms; Utility to bypass: 0ms

Overload

≤110% overload 60 min; ≤150% overload 1 min,to Bypass
Bypass mode:135% overload long time; >1000% overload 100 ms

 Backfeed protection

Support

Alarm

Overload, utility abnormal, UPS fault, battery low, etc.

Protection

Short circuit, overload, over temperature, battery low, fan fault alarm.

 Remote LCD

Support

Communication
interface

USB, RS232, RS485, Parallel port, dry contact, Intelligent slot, LBS, SNMP card (optional), Relay card (optional)

ENVIRONMENT
Operating temperature

0~40℃

Storage
temperature

25~55℃(No battery)

Humidity range

0~95% (Non-condensing)

Altitude

<1500m. When >1500m, derating power for use

Noise level

<62db

<63dB

 <65dB

PHYSICAL
Dimension
D×W×H (mm)

850x442x1100

Net weight (kg)

147

152 200

230

STANDARDS
Safety

IEC/EN62040-1,IEC/EN60950-1

EMC

IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8