MODEL |
EVO1000RT-MM |
EVO2000RT-MM |
EVO3000RT-MM |
Capacity |
1000VA/ 900W |
2000VA/ 1800W |
3000VA/ 2700W |
INPUT |
Nominal voltage |
208/220/230/240Vac |
Input voltage range |
110~300Vac (176~280Vac @ 100% load) |
Frequency range |
40~70Hz (50/60Hz Auto-Sensing) |
Power factor |
≥0.99 |
OUTPUT |
Output voltage |
208/220/230/240Vac |
Power factor |
0.9 |
Voltage regulation |
±1% |
Output frequency |
Line Mode |
46~54Hz or 56~64Hz |
Bat. Mode |
(50/60±0.1%)Hz |
Crest factor |
3:01 |
Harmonic distortion (THDv) |
≤3% Linear load |
≤5% Non linear load |
Transfer time |
AC mode to Bat.Mode |
0ms |
Inverter to Bypass |
4ms (Typical) |
Output waveform |
Pure Sinewave |
EFFICIENCY |
|
AC mode |
89% |
91% |
92% |
Battery mode |
85% |
87% |
88% |
BATTERY |
Battery number |
2 |
4 |
6 |
Capacity (Standard unit) |
9Ah/12V |
Typical recharging time |
4 hours (to 90% of full capacity) |
Charging voltage |
27.4Vdc±1% |
54.8Vdc±1% |
109.6Vdc±1% |
Charging current (Max) |
1Ah |
INDICATORS |
LED display |
Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault |
LCD display |
Input voltage,Input frequency,Output voltage,Output frequency,Load percentage, |
Battery voltage,Inner temperature& Remaining battery backup time |
ALARM |
Battery mode |
Beeping every 4 seconds |
Battery low |
Beeping every second |
Overload |
Beeping twice every second |
Fault |
Continously beeping |
PHYSICAL |
Dimension W x D×H (mm) |
440 x 325 x 86.5 |
440 x 460 x 86.5 |
440 x 600 x 86.5 |
Net weight (kg) |
8 |
11 |
15 |
ENVIRONMENT |
Operating temperature |
0℃~40℃ |
Storage temperature |
-25℃~55℃ |
Humidity range |
20~95%RH @ 0~40℃ (Non condensing) |
Altitude |
<1500m,derating required when>1500m |
Noise level |
<50db at 1 Meter |
STANDARDS |
Safety |
IEC/EN62040-1,IEC/EN62477-1 |
EMC |
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |