EVD Plus Tower 6.0

EVD Plus Tower 6.0

Part Number :EVD6T-MM

Desciption:

  • Complete protection from blackout, voltage fluctuations (overvoltages and undervoltages), lightning (with upstream arrester), frequency variations, surges, harmonics, voltage distortions
  • Recommended for Data Centers, Local Area Network (LAN ), Electro-medical, Industry processes, Virtual servers, Pellet stoves, Thermo-fireplaces, Boilers for home heating
  • Convertible format (Rack 19″ or Tower) with adjustable display
  • Hot Swap batteries
  • Intelligent slot for SNMP card o Dry Contact
  • On-Line Double Conversion technology transformerless (VFI-SS-111)
  • Active PFC circuit (0.99)
  • Compatibility with generating set
  • Battery charging system managed by microprocessor
  • Static bypass
MODEL

EVD6T-MM

EVD10T-MM

Capacity

6000VA/ 5400W

10000VA/ 9000W

INPUT
Nominal voltage

208/220/230/240Vac

Input voltage range

110~286Vac

Frequency range

40~70Hz (50/60Hz Auto-Sensing)

Power factor

≥0.99

Max.voltage:220V:+25% (Optional+10%,+15%,+20%) 230V:+20% (Optional+10%,+15%,+20%)

Bypass voltage range

240V:+15% (Optional+10%)

Min.voltage:-45% (Optional-20%,-30%)

OUTPUT  
Output voltage

208/220/230/240Vac

Power factor

0.9

Voltage regulation

±1%

Output frequency Line Mode

±1%/±2%±/±4%/±5%/±10% of the rated frequency (Optional)

Bat. Mode

(50/60±0.1%)Hz

Crest factor

3:01

Harmonic distortion (THDv)

≤2% Linear load

≤5% Non linear load

Transfer time AC mode to Bat.Mode

0ms

Inverter to Bypass

0ms

Output waveform

Pure Sinewave

Overload Line Mode

Load≤110% last 60min; ≤125% last 10min; ≤150% last 1min; >150% turn to bypass mode immediately

Bypass Mode

40A (Breaker)

63A (Breaker)

fficiency

94%

BATTERY  
Battery voltage

216/240Vdc (Adjustable)

Capacity (Standard unit)

9Ah/12V (7Ah/12V optional)

Typical recharging time

6~8 hours (to 90% of full capacity)

Charging current

1A (Standard unit); Long run unit Max.current 10A (Charging current can be set according to battery capacity)

INDICATORS
LED display

Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault

LCD display

Input voltage,Input frequency,Output voltage,Output frequency,Load percentage,

Battery voltage,Inner temperature& Remaining battery backup time

ALARM  
Battery mode

Beeping every 4 seconds

Battery low

Beeping every second

Overload

Beeping twice every second

Fault

Continously beeping

PHYSICAL
Dimension W x D×H (mm)

191×460×720

Net weight (kg)

69

71

ENVIRONMENT  
Operating temperature

0℃~40℃

Storage temperature

-25℃~55℃

Humidity range

20~95%RH @ 0~40℃ (Non condensing)

Altitude

<1500m,derating required when>1500m

Noise level

<55db at 1 Meter

<58db at 1 Meter

STANDARDS  
Safety

IEC/EN62040-1,IEC/EN62477-1

EMC

IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8